YCQ1F series excitation type Automatic Transfer Switch (ATS)

YCQ1F series excitation type Automatic Transfer Switch (ATS)

The YCQ1F series automatic transfer switch consists of a load isolation switch (without overload and short-circuit protection mechanism) and an intelligent
controller. The switch adopts an excitation type transfer mechanism, which provides faster switching speed.
It also employs a new microcomputer control system for intelligent monitoring and control, strong electromagnetic compatibility, long-term continuous operation, and stability and reliability.
The split-type product can be equipped with an LCD display controller, which is easy to operate, has clear indications, and provides a user-friendly human-machine interface.

General

The YCQ1F series automatic transfer switch consists of a load isolation switch (without overload and short-circuit protection mechanism) and an intelligent controller. The switch adopts an excitation type transfer mechanism, which

provides faster switching speed. It also employs a new microcomputer control system for intelligent monitoring and control, strong electromagnetic

compatibility, long-term continuous operation, and stability and reliability. The

split-type product can be equipped with an LCD display controller, which is easy to operate, has clear indications, and provides a user-friendly human-machine

interface.

The YCQ1F series automatic transfer switch is suitable for single-phase two-

wire/three-phase four-wire dual power supply networks with AC 230V/AC 400V    rated operating voltage and rated current up to 630A. It is used to disconnect the load circuit from one power source and connect it to another power source. The   transfer switch has self-action and optional manual operation features.

Standards: IEC 60947-6-1

 

Features

The product consists of two parts: the switch body and the intelligent ATS   controller. The switch body with an electrical and mechanical interlock. The product used solenoid actuate, double wire loop DC pulse operation, The

operation power of the conversion controller adopts the line voltage 220V of main standby power supply.No additional control power.

Type designation

 

Operating conditions

1.Ambient air temperature

Limit of temperature: -5℃ ~ +40℃ .

The average no more than +35℃ within 24 hours. 2.Transportation and storage

Limit of temperature: -25℃ ~ +60℃,

The temperature can be up to +70℃ within 24 hours. 3.Altitude ≤ 2000m

4.Atmospheric condition

When the temperature is +40℃, the air relative humidity should not exceed 50%, only under lower temperature can allow for higher relative humidity. If the

temperature is 20℃, the air relative humidity could up to 90%, Special measures should be taken for occasional condensation due to humidity changes.

5.Pollution level: Grade 3

6.Electromagnetic compatibility: Environment B

Technical date

Type YCQ1F-63 YCQ1F-125 YCQ1F-250 YCQ1F-400 YCQ1F-630
Positions II
Iusulation Voltage(V) AC690V
Rated voltage Ue(V) AC400V
Structure Type Y:Integral type Default:Splie type
Pole 2P/3P/4P
Rated current(A) 16,20,25,32,

40,50,63

80,100,125 125,140,160,

180,200,

225,250

225,250,315,350,400 400,500,630
Rated control current (A) 5 7
Control power voltage(V) AC120V/AC230V
Rated short circuti current (kA) 10
The rated impulse

withstand voltage(kV)

8
Contact transfer time(ms) ≤50
Operating transfer time(ms) 300-500
Usingzation Category AC33B
Auxiliary switch I、IIpower:2normalopen;2normalclosed;Capacity:10A/AC250V
 

Service life

Mechanical 20000 20000 17000 17000 17000
Electric 6000 6000 6000 6000 6000

Technical date

Type YCQ1F-63 YCQ1F-125 YCQ1F-250 YCQ1F-400 YCQ1F-630 YCQ1F-63 YCQ1F-125 YCQ1F-250 YCQ1F-400 YCQ1F-630
Positions III III
Iusulation Voltage(V) AC690V AC690V
Rated voltage Ue(V) AC400V AC400V
Structure Type Y:Integral type Default:Splietype
Pole 2P/3P/4P 2P/3P/4P
 

Rated current(A)

16,20,25,32,

40,50,63

 

80,100,125

125,140,

160,180,

200,225,

250

225,250,315

350,400

,  400,500,

630

16,20,25,

32,40,

50,63

 

80,100,125

125,140,160,

180,200,

225,250

225,250,

315,350,

400

400,500,

630

Rated control current(A) 6 8 6 8
Control power voltage(V) AC120V/AC230V AC120V/AC230V
Rated short circuti current (kA) 10 12.6 5 10 12.6
The rated impulse

withstand voltage(kV)

8 8
Contact transfer time(ms) ≤150 ≤150
Operating transfer time (ms) 300-500 300-500
Usingzation Category AC33iB AC33iB
Auxiliary switch I、IIpower:2normalopen&2normalclosed;Capacity:10A/AC250V I、IIpower:2normalopen&2normalclosed;Capacity:10A/AC250V
 

Service life

Mechanical

20000 20000 20000 4000 4000 20000 20000 20000 4000 4000
Electric 6000 6000 6000 1000 1000 6000 6000 6000 1000 1000

 

Controller function

Product s Type Y1 Y2
Installatio n method Split type
Display mode Indicator light Display mode
Rated duty Uninterruptd duty
Self-input and self restore
Self-input and without self restore
Normal port and standby port share to each other
Generator auto-start function
Normal power detect Four-phase lacking phase detection,three-phase over-voltage/under-voltage detection
Standby power detect
Passive fire protection input
Active fire protection input(DC9-36V)
Active fire control input
Voltage real-time display
Normal power and standby power indication
Normal power and standby power

over-voltage/under-voltage adrustable

Generator start and stop time adjustable   (F/F1)
Programmable output
RS485 communicating function

Wiring diagram

滚动至顶部