YCB9-63 MCB

YCB9-63 MCB

1. Overload protection
2. Short circuit protection
3. Controlling
4. Used in residential building, non-residential building, energy source industry and infrastructure.
5. According to the type of instantaneous release classified as follows : type B(3-5)ln, type C(5-10)ln, type D(10-20)ln

1.Overload protection

2.Short circuit protection

3.Controlling

4.Used in residential building,non-residential building,energy source industry and infrastructure

5.According to the type of instantaneous release classified as follows:type B(3-5)ln,type C(5-10)ln,type D(10-20)ln

Selection

Type Test current Tripping time Expected result Type Test current Tripping time Expected resut
B,C,D 1.13In t≤1h(In≤63A Not tripping B 3In t≤0.1s Not tripping
1.13In t≤2h(In>63A) C 5In t≤0.1s
B,C,D 1.45In t<1h(In≤63A) Tripping D 10In t≤0.1s
1.45In t<2h(In>63A) B 5In t<0.1s Tripping
B,C,D 2.55In 1s<t<60s(In≤32A) Tripping C 0In t<0.1s
2.55In 1s<t<120s(In>32A) D 20In <0.1s

Curve

YCB9-63-Curve

Technical data

Type Standard IEC/EN 60898-1
Electrical
features
Rated current In A 1,2,4,6,10,16,20,25,32,40,50,63
Poles P 1,2,3,4
Rated voltage Ue V 230/400
Insulation voltage Ui V 500
Rated frequency Hz 50/60
Rated breaking capacity A 45,006,000
Rated impulse withstand voltage(1.2/50)Uimp V 4500(80A)/6000(1-63A)
Dielectric test voltage at ind.Freq.for 1min kV 2
Pollution degree 2
Thermo-magnetic release characteristic B,C,D
Mechanical
features
Electrical life t 6000
Mechanical life t 20000
Protection degree IP20
Reference temperature for setting of thermal
element
30
Ambient temperature
(with daily average≤35℃)
-5~+40
Storage temperature -25~+70
Installation Terminal connection type Cable/Pin-type busbar
Terminal size top/bottom for cable  mm² 25
 AWG 18-3
Terminal size top/bottom for busbar  mm² 25
 AWG 18-3
Tightening torque  N*m 2
In-lbs 18
Mounting On DIN rail EN 60715(35mm)by means of fast clip
Connection From top or bottom

Overall and mounting dimensions(mm)

YCB9-63-Overall