YCB6 Miniature Circuit Breaker(MCB)

YCB6 Miniature Circuit Breaker(MCB)

YCB6-63 miniature circuit breaker(circuit breaker) is applicable to the circuit with AC50Hz/60Hz, rated voltage of no more than 400V, rated current up to 63 A for overload protection and short circuit protection. This product can be applied to various places such as industrial, commercial, tall buildings,and residential houses.

Standard: IEC60898-1

Type designation

YCB6-63 MCB Type designation

Technical data

Type Standard IEC/EN 60898-1
Electrical
features
Rated current In A 1,2,3,4,6,10,16,20,25,32,40,50,63
Poles P 1,2,3,4
Rated voltage Ue V 230/400
Insulation voltage Ui V 500
Rated frequency Hz 50/60
Rated breaking capacity A 30,004,500
Rated impulse withstand voltage(1.2/50)Uimp V 4000
Dielectric test voltage at ind.Freq.for 1min kV 2
Pollution degree 2
Thermo-magnetic release characteristic B,C,D
Mechanical
features
Electrical life t 6000
Mechanical life t 20000
Protection degree IP20
Reference temperature for setting of therma
element
30
Ambient temperature
(with daily average≤35℃)
-5~+40
Storage temperature -25~+70
Installation Terminal connection type Cable/Pin-type busbar
Terminal size top/bottom for cable  mm² 25
 AWG 18-3
Terminal size top/bottom for busbar  mm² 25
 AWG 18-3
Tightening torque  N*m 2
In-lbs 18
Mounting On DIN rail EN 60715(35mm)by means of fast clip device
Connection From top or bottom

Selection

B,C,D 1.13ln t≤1h(In≤63A) Not tripping B 3In t≤0.1s Not tripping
1.13ln t≤2h(In>63A) C 5In t≤0.1s
B,C,D 1.45In t<1h(In≤63A) Tripping D 10ln t≤0.1s
1.45ln t<2h(In>63A) B 5In t<0.1s Tripping
B,C,D 2.55ln 1s<t<60s(In≤32A) Tripping C 10ln t<0.1s
2.55In 1s<t<120s(In>32A) D 20ln t<0.1s

Curve

63A Circuit Breaker Curve

Temperature drop correction table

The maximum allowable current of the circuit breaker is related to the ambient temperature of the circuit breaker. The ambient temperature refers to the temperature in the distribution box or switch cabinet where the circuit breaker is installed. The reference temperature of various circuit breakers can be found in the values of the colored rows in the table.

Product standard: GB/T10963.1 IEC60898-1 (household standard)
temperature(℃) -5 0 5 10 15 20 25 30 35 40 45
Rated current
1A 1.16 1.14 1.11 1.09 1.07 1.05 1.02 1.00 0.98 0.95 0.92
2A 2.30 2.26 2.22 2.18 2.13 2.08 2.04 2.00 1.96 1.92 1.88
4A 4.72 4.63 4.53 4.43 4.32 4.22 4.11 4.00 3.89 3.77 3.65
6A 6.97 6.84 6.71 6.57 6.43 6.29 6.15 6.00 5.85 5.69 5.53
10A 12.25 11.95 11.65 11.34 11.02 10.69 10.35 10.00 9.64 9.26 8.86
16A 18.72 18.35 17.98 17.60 17.22 16.82 16.42 16.00 15.57 15.13 14.68
20A 23.24 22.80 22.36 21.91 21.45 20.98 20.49 20.00 19.49 18.97 18.44
25A 29.12 28.57 28.01 27.43 26.85 26.24 25.63 25.00 24.35 23.69 23.01
32A 37.18 36.49 35.78 35.05 34.32 33.56 32.79 32.00 31.19 30.36 29.50
40A 46.66 45.77 44.86 43.93 42.98 42.01 41.02 40.00 38.96 37.88 36.78
50A 58.57 57.43 56.26 55.06 53.84 52.59 51.31 50.00 48.65 47.27 45.84
63A 74.73 73.17 71.57 69.94 68.27 66.56 64.81 63.00 61.14 59.22 57.24

Overall and mounting dimensions(mm)

din rail circuit breaker overall

General

This series circuit breaker accessories are used in household, building and other electrical circuits with YCB6-63 circuit breaker cooperated for
remote control and diferent accessories selected for different needs, featured with auxiliary signal, opening and closing status indication, and
even alarm signal function for better protection on the circuit, personal and property safety.

Type designation

 YCB6 Circuit Breaker Type designation

Function

Accessory name Code   Function
Auxiliary contact OF Provide auxiliary signal and control auxiliary circuit
Alarm contact SD When the circuit breaker is due to a fault,the alarm signal would work and indicate.
Shunt release MX Over the range of 70%~110%of the rated control supply voltage,the release should trip the
circuit breaker to protect the circuit.
Shunt release+
Auxiliary contact
MX+OF Remote control of circuit and control the auxiliary circuit by auxiliary contact.
Over-voltage and
under-voltage release
MV+MN When the rated voltage 230V increase to 270V+/-5%or reduce to 170V+/-5%,
the circuit breaker should trip for over-voltage and under-voltage protection.

installation

Al the electrical accessories should be installed at the side of the circuit breaker,details are shown in the figure below.(Remark:eeach MCB can be installed with 3(MAX.)indicating accessories.)

 YCB6-63 series MCB

Operating Conditions

● Ambient temperature:-5℃~+40℃;

● Altitude:Below 2000m;

● Environment:The medium should be no risk of blasting and can’t corrode the metal and damage insulating gas as well as conductive dust;

● Installation:35mm standard din rail.

Technical data

Auxiliary contact and Alarm contact technical parameters

Accessory name Rated current(A) Number of contacts
AC 380V AC 220V AC 110V
Auxiliary contact
OF
3 6 1 1NO 1NC
Alarm contact
SD
3 6 1 1NO 1NC

Shunt release,Shunt release+Auxiliary contact technical parameters

Accessory name Rated insulation
voltage Ui
Rated control
voltage Us
Tripping power
consumption
(W or VA)
Operation voltage
Us
Shunt release
MX
415V AC/DC:220~380V
110~220V
240 0.7~1.1
AC/DC:24~48V 120

Under-voltage &Over-voltage Release technical parameters

YCB6-63 Miniature Circuit Breaker parameter